JA-180G Wireless gas leak detector
SKU: JA-180G
JA-180G Wireless gas leak detector For Burglar Alarm and Security Installations & Home Automation Jablotron Burglar Alarm Security System is work to : Schools, House, Villa, Mansion, Village houses, Apartment, Shopping Mall, Ground Level Shops, Upper Level Shops…
Sensitivity (concentration):
Methane Propane Iso-butane
First level 10 ± 3% LEL (0.44% vol) 18 ± 3% LEL (0.30% vol) 23 ± 3 % LEL (0.30% vol)
Second level 18 ± 3% LEL (0.80% vol) 30 ± 3% LEL (0.50% vol) 40 ± 3 % LEL (0.50% vol)
LEL = Lower Explosive Limit (100%) according to IEC 60079-20-1: for methane 4.4% volume concentration. For propane 1.7% vol, for iso-butane 1.3% vol, calibrated in the production of iso-butane
Specifications:
Mains | 230 V ( 10 to -15%) / 50 Hz, about 2 W, protection class II |
---|---|
Beep | 94 db / 0.3 m |
Relay output | optional response to 1st or 2nd level |
Capacity of relay | max 230 V / 5 A |
Operational temperature range | -10 ° C to 40 ° C |
Relative humidity | 25 to 75% |
Storage temperature range | -20 ° C to 50 ° C |
Stabilization time | 90 s |
Response time | up to 10 s |
Detection method | catalytic combustion |
Housing | IP 30 (EN 60 529) |
Communication band | 868.1 MHz, Jablotron protocol |
Communication range | about 200 m in an open area |
Dimensions, weight | 101 x 74 x 39, 210 g |
Operating conditions | ERC REC 70-03 |
Designed to operate at normal atmospheric pressures | 86 to 106 kPa |
Meets | EN 50194-1, IEC 60079-29-1, IEC 50130-4, EN 55022, ETSI EN 300220, EN 60950-1 |
Intended for non-explosive areas – Zone 2 | EN 60079-10 |
VVUÚ certified at certification body No 3076 |